Project Description

SM6 24kV

An Air-Insulated modular switchboard SM6 that guarantees high-reliability for your underground secondary distribution, flexible and easy to install and operate

SM6 24kV

Modular air-insulated Switchboard up to 24 kV

An Air-Insulated modular switchboard SM6 24kV that guarantees high-reliability for your underground secondary distribution, flexible and easy to install and operate By combining these recognizable values and innovative solutions, we can respond to the most complex requirements for the medium voltage distribution and protection of the medium voltage equipment in distribution and industrial transformer stations. Your imagination, our realization.

Get in touch
sm6 24kv sne energy
Catalog SM6 24kV
Additional information
Rated voltage Ur kV 7,2kV 12kV 17,5kV 24kV
Insulation level Ud 50Hz, 1min (kV rms) 20kV 28kV 38kV 50kV
Up 1,2/50µs (kV peak) 60kV 75kV 95kV 125kV
Rated current In 400A – 630A – 1250A
Short-time withstand current Ik/tk 25kA/1sec 630A – 1250A
20kA/1sec 630A – 1250A
16kA/1sec 630A – 1250A
12,5kA/1sec 400A – 630A – 1250A
Ima 62,5kA 630A NA
50kA 630A
40kA 630A
31,25kA 400A – 630A
  • Metal enclosed units
  • Classes PI (insulating partition)
  • Classes LSC2A (loss of service continuity classes)
  • Units in switchboard: IP3X
  • Between compartments: IP2X
  • Cubicle: IK08
  • Internal arc withstand:
    • Basic version:
      • 12,5kA 1sec, IAC: A-FL
    • Advanced version:
      • 12,5kA 1sec, IAC: A-FLR
      • 16kA 1sec, IAC: A-FLR & IAC: A-FL
      • 20kA 1sec, IAC: A-FLR & IAC: A-FL
  • Working temperature:
    • less than or equal to 40 ° C
    • less than or equal to 35 ° C mean 24-hour value
    • greater than or equal to -5 ° C
  • Elevation:
    • Less than or equal to 1000m
    • Over 1000m, correction factors apply (please contact us)
  • Solar radiation
    • Is not allowed
  • Seismic
    • Class 2
  • IM – switch unit
  • IMC – unit with current measuring
  • IMB – Switch unit with earthing disconnector, right or left outgoing line
  • IMM – switch and measurement unit, right or left outgoing line
  • NSM – power supply for main incoming line on right or left and cables for standby line (Automatic Transfer System)
  • QM – Fuse-switch combination unit
  • QMC – Fuse-switch combination unit
  • QMB – Fuse-switch combination unit right or left outgoing line

Switch mechanism:

  • CI1 operating mechanism
    • Disconnector manipulation

Independent-operation opening and closing by lever or motor

Independent-operation opening by push-button (O) or trip units.

  • Earthing switch manipulation

Independent-operation opening and closing by lever

  • Motor option – Standard or severe environment and communication
  • Closing – release shunt trip

A mechanical interlocking of the disconnector and earthing switch was performed on the mechanism in order to prevent incorrect manipulation.

  • DM1-A – Single-isolation, disconnectable circuit breaker unit
  • DM1-D – Single-isolation, disconnectable circuit breaker unit right or left outgoing line
  • DM1-M – Single-isolation,disconnectable circuit breaker and measurement unit right outgoing line
  • DM1-S – Single-isolation, disconnectable circuit breaker unit with autonomous protection
  • DM2– Double-isolation, disconnectable circuit breaker unit right or left outgoing line

Switch mechanism:

  • CS operating mechanism
    • Disconnector manipulation

Independent-operation opening and closing by lever.

  • Earthing switch manipulation

Independent-operation opening and closing by lever

A mechanical interlocking of the disconnector and earthing switch was performed on the mechanism in order to prevent incorrect manipulation.

Switch mechanism:

  • RI operating mechanism
    • Switch function

Independent-operation closing in two steps:

First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit.

Independent-operation opening by push-button (O) or trip units.

  • Opening releases – Mitop (low energy), shunt trip
  • Closing release – shunt trip
  • Motor option – Standard or severe environment and communication

A key-type interlock (type 50) is fitted on the units as standard to prevent the wrong sequence of manipulations between the switch and the disconnector (the disconnector does not switch off under load).

  • DM1-W – Single-isolation, disconnectable circuit breaker unit
  • DM1-Z – Withdrawable single-isolation circuit breaker unit right outgoing line

NOTE: The circuit breaker is pulled out of the cell (there is no option to pull the switch from inside the cell). This allows quick circuit breaker replacement.

Switch mechanism:

  • CS operating mechanism
    • Disconnector manipulation

Independent-operation opening and closing by lever.

  • Earthing switch manipulation

Independent-operation opening and closing by lever

A mechanical interlocking of the disconnector and earthing switch was performed on the mechanism in order to prevent incorrect manipulation.

Switch mechanism:

  • RI operating mechanism
    • Switch function

Independent-operation closing in two steps:

First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit.

Independent-operation opening by push-button (O) or trip units.

  • Opening releases – Mitop (low energy), shunt trip
  • Closing release – shunt trip
  • Motor option – Standard or severe environment and communication

A key-type interlock (type 50) is fitted on the units as standard to prevent the wrong sequence of manipulations between the switch and the disconnector (the disconnector does not switch off under load).

  • DMV-A – Single-isolation circuit breaker unit
  • DMV-D – Single-isolation circuit breaker unit right outgoing line

Switch mechanism:

  • CIT operating mechanism
    • Disconnector manipulation

Independent-operation closing and opening by lever or motor.

  • Earthing switch manipulation

Independent-operation opening and closing by lever

A mechanical interlocking of the disconnector and earthing switch was performed on the mechanism in order to prevent incorrect manipulation.

  • Motor option – Standard or severe environment and communication

Switch mechanism:

  • P2 operating mechanism
    • Switch function

Independent-operation closing in two steps:

First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit.

Independent-operation opening by push-button (O) or trip units.

  • Opening releases – Mitop (low energy), shunt trip
  • Closing release – shunt trip
  • Motor option – Standard or severe environment and communication
  • DMVL-A – Single-isolation, disconnectable circuit breaker unit
  • DMVL-D – Single-isolation, disconnectable circuit breaker unit right outgoing line

Switch mechanism:

  • CS operating mechanism
    • Disconnector manipulation

Independent operation of switching on and off with a manipulative wire

  • Earthing switch manipulation

Independent-operation opening and closing by lever

A mechanical interlocking of the disconnector and earthing switch was performed on the mechanism in order to prevent incorrect manipulation.

Switch mechanism:

  • RI operating mechanism
    • Switch function

Independent-operation closing in two steps:

First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit.

Independent-operation opening by push-button (O) or trip units.

  • Opening releases – Mitop (low energy), shunt trip
  • Closing release – shunt trip
  • Motor option – Standard or severe environment and communication